Installation Guide LP33 Series 80 & 100 UL S1

3.9.2 Dual input utility (option)

Fig. 3.9.2-1 Dual Input Utility (option)

Dual input utility

On request, the UPS can be delivered for

Dual Input Utility.

Two independent lines (F2 and F3)
supply separately the rectifier and the
Bypass inputs

With this configuration, when the
rectifier-input fuses are opened, the
Automatic Bypass and the Manual
Bypass
are supplied by the other line.

LP

S

33U_080

-100

_

C

onnection sepa

rate

_0

1US

L3

L1

L2

N2

X3

Load

X1

Utility 1

X4

Battery

GND

GND

L3

L1

L2

N1

X2

Utility 2

L3

L1

L2

N

-

0 +

Fig. 3.9.2-2 Terminals for Dual Input Utility

X1 Utility 1 - Rectifier Input Utility connection

L1-1 = Rectifier Phase A
L2-1 = Rectifier Phase B
L3-1 = Rectifier Phase C
N1 =

Utility

Neutral

GND = Main Ground

X2 Utility 2 - Bypass Input Utility connection

L1-2 = Bypass Phase A
L2-2 = Bypass Phase B
L3-2 = Bypass Phase C
N =

Utility

Neutral

X3 Load - Output Load connection

L1 = Load

Phase

A

L2 = Load

Phase

B

L3 = Load

Phase

C

N2 =

Load

Neutral GND = Load Ground

Connect wire to the Terminals by using
appropriate tools and appropriate torque
.

Torque specification for Input / Output and DC
power connections on Terminals
: Section 3.8.1.

Max. rating X1, X2, X3 & X4 terminals:

2 x AWG 4/0 - Use 167°F (75°C) copper wire

NOTE !

For UPS correct operation, the input utility phase rotation must be clock-wise.
Inside the UPS, all neutrals N1
and N2 are connected together.
This UPS is designed to operate in a wye-configured electrical system with a solidly
grounded neutral.