GE Industrial Solutions LP33 Series 80 & 100 Installation Guide User Manual
Page 24
Modifications reserved
Page 24/47
OPM_LPS_3UI_80K_M10_1US_V010.doc
Installation Guide LP33 Series 80 & 100 UL S1
3.7.4 General data table for current protection and wire sizing
Fig. 3.7.4-1 Common Input Rectifier & Bypass
Fig. 3.7.4-2 Dual Input Rectifier & Bypass (option)
The AC values below are current ratings per phase.
These maximum and nominal ratings should be considered when choosing the
appropriate AC over current protection device.
NEC (National Electric Code) Section 210-20 a rules must be applied.
DC current rating is the maximum battery discharge current which the UPS allows.
AC Input
AC Input Rectifier
AC Input Bypass
DC Input (*)
F2
UPS Model
F1
Nom. Max.
F3 FTM3
LP33 Series 80
229 A
229 A
250 A
222 A
292 A
LP33 Series 100
285 A
285 A
316 A
278 A
365 A
(*) Nominal voltage rating: 2 x 144Vdc