3.9 ELECTRICAL CONNECTIONS

WARNING !

The connections to and from the UPS must be executed by QUALIFIED PERSONNEL
ONLY. Refer to the “Safety Rules - Installation
” described on page 6.

3.9.1 Common input utility

Fig. 3.9.1-1 Common Input Utility

Common Input Utility

The UPS delivered in standard version

has Common Input Utility.
Only one input line (F1) supplies both
Rectifier and Bypass input terminals.

Bear in mind that when the utility
fuses are opened there is a supply
failure to the rectifier as well as to the
Automatic Bypass and Manual Bypass.

L3

L1

L2

N2

X3

Load

X1

Utility 1

X4

Battery

GND

GND

LP

S

33U_0

80-

100

_Con

ne

ct

io

n co

mm

on

_0

1U

S

L3

L1

L2

N1

-

0 +

Fig. 3.9.1-2 Terminals for Common Input Utility

X1 Utility 1 - Input Utility connection

L1 = Rectifier + Bypass Phase A
L2 = Rectifier + Bypass Phase B
L3 = Rectifier + Bypass Phase C
N1 = Utility

Neutral

GND = Main Ground

X3 Load - Output Load connection

L1 = Load

Phase

L1

L2 = Load

Phase

L2

L3 = Load

Phase

L3

N2 = Load

Neutral GND = Load Ground

Max. rating X1, X3 and X4 terminals:

2 x AWG 4/0 - Use 167°F (75°C) copper wire

Connect wire to the Terminals using appropriate tools and appropriate torque.

Torque specification for Input / Output and DC power connections on Terminals: Section 3.8.1.

NOTE !

For UPS correct operation, the input utility phase rotation must be clock-wise.
Inside the UPS, all neutrals N1
and N2 are connected together.
This UPS is designed to operate in a wye-configured electrical system with a solidly
grounded neutral.