Mechanical assembly of the UPS and the battery cabinet 26” / 650mm

NOTE !

Mechanical assembly of the UPS and the battery cabinet must be performed by
QUALIFIED SERVICE PERSONNEL only.
The UPS cabinet and the battery cabinet must be installed on leveled floor.


UPS with battery cabinet 26” / 650mm

Bolt M8x25

tensilock

Detail showing the

mechanical assembly

of the UPS and battery cabinets 26"/650mm.

To bolt only on the front side.

Battery cabinet frame 26"/650mm

Nut M8 tensilock

UPS cabinet frame

Q2

I ON

0 O

FF

F11-12-13

FTM3

Q1

I ON

0 O

FF

UPS cabinet

Battery cabinet

26"/650mm

6.5"

165mm

37

.4

"

950mm

68.3

"

173

5m

m

A

A

A

LPS33U_080-100_UPS+Battery cabinet 0660_01

A

Fig. 3.9.3-1 Mechanical assembly of the UPS and the battery cabinet 26” / 650mm

Align the cabinets together, with the Battery cabinet on the left side. In case of multiple battery cabinets,
align first beside of the UPS the battery cabinets 26” and then left the wider battery cabinets 48”.
Pay attention, that no loose cables are trapped when pushing the cabinets together.
Join the cabinets with bolts trough the fixing holes as illustrated in drawing Fig. 3.9.3-1 and 3.9.3-2 /
detail A & B
.
Once finally positioned, the two cabinets have to be connected together with the connection cables,
see Fig 3.9.3-3 (Battery cabinet 26”/650mm), Fig 3.9.3-4 (Battery cabinet 48”/1215mm) and Fig 3.9.3-
5
(Battery cabinet 26”/650mm and 48”/1215mm).


UPS with battery cabinet 26” / 650mm and 48” / 1215mm

LPS33U_080-100_UPS+Battery cabinet 1215_01

Detail showing the mechanical assembly
of the UPS and battery cabinets 26"/650mm or/and 48"/1215mm.

To bolt only on the front side.

Q2

I ON

0 O

FF

F11-12-13

Q1

I ON

0 O

FF

A

Battery cabinet

48"/1215mm

UPS cabinet

Battery cabinet

26"/650mm

Battery cabinet frame

Nut M8 tensilock

UPS cabinet frame or
battery cabinet frame

A

FTM3

6.

5"

165m

m

37

.4

"

950m

m

68.

3"

17

35m

m

A

A

A

Bolt M8x25

tensilock

A

FTM3

A

Fig. 3.9.3-2 Mechanical assembly of the UPS and the battery cabinet 26” / 650mm and 48” / 1215mm