Installation Guide LP33 Series 80 & 100 UL S1

Size of Branch Circuit Over current Protection - All Models:

"CAUTION - To reduce the risk of fire, only connect UPS to a circuit provided with (see below)

maximum amperes branch circuit over current protection in accordance

with the NEC (National Electric Code), NSI / NFPA 70

AC Input

AC Input Rectifier

AC Input Bypass

DC Input (*)

UPS Model

F1 F2 F3

FTM3

LP33 Series 80

350 A

350 A

350 A

400 A

LP33 Series 100

400 A

400 A

400 A

400 A

(*) Nominal voltage rating: 2 x 144Vdc




Wire sizing according to NEC Section 210-20 (a) Table 310-16
Use 167°F (75°C) copper wire

Wiring requirements:
AC INPUT:

3-Phase, 4 wire plus Ground

AC OUTPUT:

3-Phase, 4 wire plus Ground

DC INPUT:

3 wire (positive, negative and neutral) plus Ground





Maximum cable diameter that terminals can accept.

Refer to torque specifications table for torque requirements.

UPS Model

Rectifier Input

Bypass Input

DC Input

AC Output

GND

LP33 Series 80

4x(2xAWG 3/0)

4x(2xAWG 3/0)

3x(2xAWG 4/0)

4x(2xAWG 3/0)

AWG 2/0

LP33 Series 100 4x(2xAWG 4/0)

4x(2xAWG 4/0)

3x(2xAWG 4/0)

4x(2xAWG 4/0)

AWG 2/0