1 dimensions and weight, Dimensions and weight – GE Industrial Solutions SG Series 750 T12 UL S2 Installation Guide User Manual

Page 13

Advertising
background image

Modifications reserved

Page 13/49

OPM_SGS_ISG_M75_M75_2US_V010.doc

Installation Guide SG Series 750 UL S2 & SG Series 750 T12 UL S2

3.1.1 Dimensions and weight

SGS_75

0_UPS d

imension

s_GE_01

Inverter ca

binet

Rectifier c

abinet

67"

1700mm

76.8

"

1950

mm

2020mm

79.5"

146.5"

3720mm

35.4"

900mm

Fig. 3.1.1-1 SG Series 750 & SG Series 750 T12 cabinet dimensions

SG Series 750 & SG Series 750 T12 UPS dimensions (W x D x H)

SG Series 750 & SG Series 750 T12 146.5x35.4x76.8

inches (3720x900x1950 mm)

SG Series 750 & SG Series 750 T12 - Inverter cabinet

79.5x35.4x76.8 inches (2020x900x1950 mm)

SG Series 750 & SG Series 750 T12 - Rectifier cabinet

67x35.4x76.8 inches (1700x900x1950 mm)

Weights SG Series 750 & SG Series 750 T12 and options

Weight

(lbs./ Kg)

Floor Load

(lbs./sq ft / Kg/m

2

)

UPS rating with

Rectifier Configuration

Rectifier Inverter Rectifier Inverter

SG Series 750 (6 pulse) with 5

th

filter

3468 / 1573

6332 / 2872

211 / 1028

324 / 1580

SG Series 750 (6 pulse) with 5

th

& 11

th

filter

3607 / 1636

6332 / 2872

219 / 1069

324 / 1580

SG Series 750 T12 (12 pulse) without filter

5002 / 2269

6332 / 2872

304 / 1483

324 / 1580

SG Series 750 T12 (12 pulse) with 11

th

filter

5141 / 2332

6332 / 2872

312 / 1524

324 / 1580


NOTE !

The weight of each single piece is marked outside the package!

Advertising