2 power connection with common input utility, Power connection with common input utility – GE Industrial Solutions SG Series 750 T12 UL S2 Installation Guide User Manual

Page 31

Advertising
background image

Modifications reserved

Page 31/49

OPM_SGS_ISG_M75_M75_2US_V010.doc

Installation Guide SG Series 750 UL S2 & SG Series 750 T12 UL S2

3.9.2 Power connection with common input utility

-

+

Neutral Load

Neutral Utility (Bypass)

SG

S_

75

0_U

P

S

connec

tio

n

common_G

E_01

_U

S

PE Input Utility

PE Load

Typical installation using
common NEMA two hole lugs

PE Load

PE Input Utility

LOAD

L3

1 - INPUT UTILITY

RECTIFIER & BYPASS

L1-1

L2-1

L3-1

Typical installation using
common NEMA two hole lugs

L2

L1

bus bars are done, the

PHASE BARRIER NOMEX SHEET

must be screwed onto the bus bars

After cable connections to the

wit 2 bolts M4x10

BR

1,

BR

2 a

nd

BR3

Fig. 3.9.2-1 SG Series 750 & SG Series 750 T12 power connections Common Input Utility


Use M12x35 bolts for the cable connections on INPUT / OUTPUT Power Wiring Bus Bars.
Cable terminations are to the Rectifier Input / Output Bus Bars as shown above.
Connect wire to the Bus Bars using appropriate tools and appropriate torque.
Torque specification for two hole lugs on Bus Bars: see Section 3.9.1.

Common Input Rectifier / Bypass

L1-1

Rectifier + Bypass Phase A

L2-1

Rectifier + Bypass Phase B

L3-1

Rectifier + Bypass Phase C

N

Utility Neutral (Bypass)

PE Input Utility

Ground

The interconnection bus bars BR1, BR2 and BR3 MUST REMAIN CONNECTED (see Fig.
3.9.3-3)
.


Output Load

L1

Load Phase A

L2

Load Phase B

L3

Load Phase C

N

Load Neutral

PE Load

Load Ground