3.7.2 Bus bars interconnection

WARNING !

All the inter cabinet wiring must be performed by QUALIFIED SERVICE PERSONNEL
only.


Inverter cabinet

Rectifier cabinet

8

9

4

3

2

1

7

6

5

10

SGS_750_S2_UPS connection cabinets_GE_01US

Fig. 3.7.2-1 Bus bars interconnections


Connection

Description of connection

Type (medium of connection)

Connection Type

(See Fig. 3.7.1-2)

1

Interconnection Bypass Line 1

1 Bus bar of size 40 x 10mm

Type 1

2

Interconnection Bypass Line 2

1 Bus bar of size 40 x 10mm

Type 1

3

Interconnection Bypass Line 3

1 Bus bar of size 40 x 10mm

Type 1

4

Interconnection for Inverter
output Line 1

1 Bus bar of size 40 x 10mm

Type 1

5

Interconnection for Inverter
output Line 2

1 Bus bar of size 40 x 10mm

Type 1

6

Interconnection for Inverter
output Line 3

1 Bus bar of size 40 x 10mm

Type 1

7

Neutral

1 Bus bar of size 80 x 10mm

Type 2

8

Positive DC bus bar

2 Flexi bars of size 5 x 40mm

Type 3

9

Negative DC bus bar

2 Flexi bars of size 5 x 40mm

Type 3

10

Inter cabinet Earthing

3 Flexi bars of size 4 x 32mm

Type 4