Installation Guide SG Series 750 UL S2 & SG Series 750 T12 UL S2

3.7.3 Control cables Interconnection

WARNING !

All the inter cabinet wiring must be performed by QUALIFIED SERVICE PERSONNEL
only.

g

SGS_750_S2_UPS connection cabinets_GE_02US

Inverter cabinet

Rectifier cabinet

3

H10

H9

4

H8

2

5

1

Fig. 3.7.3-1 Control cables interconnection

Pos.

Connection

Already connected on

Connecting to

1

Female Molex connectors
H8, H9, H10

Rectifier cabinet

Inverter cabinet
Male Molex connectors H8, H9, H10

Flat cable with connector 10 pin

Rectifier cabinet (SSM)

Rectifier cabinet
J33B – IM0174 Adapter Board

2

Flat cable with connector 26 pin

Rectifier cabinet (Inverter)

Rectifier cabinet
J19B – IM0174 Adapter Board

Male connector HAN 18

Inverter cabinet

Rectifier cabinet, see Pos. 5

Female connector HAN 18
Refer Fig 3.7.3-2

3

Male connector HAN 32

Inverter cabinet

Rectifier cabinet, see Pos. 5
Female connector HAN 32
Refer Fig 3.7.3-2

Flat cable with connector 10 pin

Inverter cabinet
P3 – IM0007 Control Board

Rectifier cabinet, see Pos. 2
J33A – IM0174 Adapter Board

4

Flat cable with connector 26 pin

Inverter cabinet
P3 – IM0007 Control Board

Rectifier cabinet
J19A – IM0174 Adapter Board

HAN connector Male
(hanging in inverter cabinet)

HAN connector Female
(fixed in Rectifier cabinet)

HAN connector Male
(hanging in inverter cabinet)

HAN connector Female
(fixed in Rectifier cabinet)

Fig. 3.7.3-2 Connection of hearting connectors (HAN connectors)

NOTE:

All these connections must be performed by

QUALIFIED SERVICE PERSONNEL only.

Proper dressing needs to be done for each cable assembly

in order to reduce the stress.

All the cables must be sufficiently (at least 10 cm) away
from all live parts.

Cable binders used to support the wiring must NOT be overly

tightened.