9

Status Indicators

LED 1 – Ethernet Link/Activity

Color LED

state

Description

On

The module sense link

Off

The module does not sense link

Green

Flash

The module is receiving/transmitting data on Ethernet

LED 2 – Module Status

LED state

Device State

Description

Steady Off

No power

-

Steady Green

Device operational

The module has an Ethernet/IP connection OR has a
healthy EGD exchange OR has a Modbus/TCP
connection.

Flashing Green

Standby

The module has no active data exchange but is ready to
be controlled.

Flashing Red

Minor fault

A recoverable minor fault has been detected. E.g., a
connection time out or EGD exchange in unhealthy state.

Steady Red

Major fault

A major internal error has been detected. E.g., hardware
fault or invalid drive type detected.

Flashing Green/Red

Self-test

The module is performing its power up testing.

LED 3 – Network Status

LED state

Network State

Description

Steady Off

No power or
no IP address

The module has no power or no IP address is configured.

Flashing Green

No connections

There are no Ethernet/IP connections established to the
module.

Steady Green

Connected

The module has at least one established Ethernet/IP
connection.

Flashing Red

Connection timeout One or more of the EtherNet/IP connections, where this

module is the target, has timed out. This state is only left if
all timed out connections are re-established or if the
module is reset.

Steady Red

Duplicate IP

The module has detected that its IP address is already in
use.

Flashing Green/Red

Self-test

The module is performing its power up testing.

Advertising