Appendix A - EGD, EtherNet/IP IO Format

25

Appendix A - EGD, EtherNet/IP IO Format

This chapter specifies the format of data that is cyclically exchange with the drive, here called IO data. This
format is used for the assembly instances on EtherNet/IP and for the exchanges P1 and C1 on EGD.

Data Consumed by the Drive

Consumed data is located in assembly instance 150 on EtherNet/IP and Produced Exchange 1(P1) on EGD.

Position Description
Word 0 (16 Bit)

Run command word

Word 1 (16 Bit)

Frequency setting (S01)

Run Command Word

15

14

13 12 11 10 9 8 7 6 5 4 3 2 1 0

RST - BX RT4 - X9 X8 X7 X6 X5 X4 X3 X2 X1 REV

FWD

FWD

1: Run forward command

REV

1: Run reverse command

X1 – X9

1: Digital input

(Each function is set by inverter’s parameter E01-E09, See drive manual)

RT4

1: Acceleration/Deceleration time 4 (Has priority over the Acc/Dec time selection by X terminal)

BX 1:

Coast-to-stop

command

RST

Alarm

reset:

0 to 1 and 1 to 0

t

min

= 20ms

Frequency Setting (S01)

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Frequency command data

Frequency is set as: Output Frequency * 20000 / Max frequency

Max frequency = F03

Reverse direction is set with a negative value