Data format [20]: transmission error code, Data format [21]: auto tuning – GE Industrial Solutions AF-300 P11_G11 Ethernet Interface User Manual

Page 43

Advertising
background image

Appendix B - Drive Parameters

37

Data Format [19]: Amperage Value Decimal Data (Positive)

Min unit 0.01, inverter capacity 30HP or below

Min unit 0.1, for 40 HP and over

Example) If F11 (electronics thermal overload relay 1 level) 107.0 A (40 HP)

107.0 x 10 = 1070 =042E

H

If F11 (electronics thermal overload relay 1 level) 3.60A (1 HP)

3.60 x 100 = 360 =0168

H

Data Format [20]: Transmission Error Code

Field Description

Code Description

1

FC (Function code) error

71

CRC error (no response)

2

Illegal address

72

Parity error (no response)

3

Illegal address (Data range error)

73

Other errors (no response)
- Framing error
- Overrun error
- Buffer full error

7

NAK
- Priority for comm.
- No privilege for writing error
- Forbidden writing error

- -

Data Format [21]: Auto Tuning

(MSB)

(LSB)

15 14 13 12

11 10 9 8 7 6 5 4 3 2 1 0

0 0 0 0 0 0

REV

FWD

Data

portion

0: Without forward rotation command

1: With forward rotation command

0: Without reverse rotation command

1: With reverse rotation command

Example) If P04 (Motor 1 auto tuning) = 1 : Forward rotation

0000 0001 0000 0001

B

= 0101

H

Advertising