Installation and Configuration

12

Bus Configuration Parameters

Some basic settings can be accessed via the keypad. For instructions how to use the keypad, see the drive’s
user manual.

Drive
parameter

Name Description

o30 Communication

rate

0 = Auto negotiate
1 = 100 Mbps, Full duplex
2 = 100 Mbps, half duplex
3 = 10 Mbps, Full duplex
4 = 10 Mbps, half duplex

o31 Disable

FTP 0 = Enable FTP server

1 = Disable FTP server

o32 Reserved

-

o33 IDLE

action 0 = If the EtherNet/IP header indicates idle, an error is sent to

the drive
1 = The run/idle bit is ignored

o34 Modbus/TCP

timeout

Sets the maximum time between Modbus/TCP commands
before a time-out is detected.
The value is multiplied with 100 ms to give the timeout from
100ms-25.5s.

Operation Configuration Parameters

These parameters configure the link option control and set the drive’s reaction upon a network loss event.

Drive
parameter

Name Description

H30 Link

function 0 = Command and freq. from drive

1 = Command from drive, freq. from option card
2 = Command from option card, freq. from drive
3 = Command and freq. from option card

o27

Loss of network
behaviour

0 = Immediate trip (ERR5)
1 = Trip after timer setting, o28
2 = Re-check after timer setting o28
3 = Ignore communication error

o28

ERR5 timer setting
(used with o27)

ERR5 timer setting, 0.0 – 60s