EtherNet/IP
20
3. Select type “ETHERNET MODULE” and click OK
4. Configure the IP address to the module and Input and Output instances. The configuration instance
is not used but requires a value. Input is set to three words and output is to two words, the data
format shall be set to “Data – INT”. Click Next>
5. Set the RPI value to 20ms or higher. Click Finish>>>
The module is now added to the PLC configuration and can be used in the PLC program. For example, to
access the drive speed, use the tag OPCG11SETN:I.Data[2].
Save the configuration and download to the PLC.
The format of the IO data is described in “Appendix A - EGD, EtherNet/IP IO Format”.