GE Industrial Solutions AF-300 P11_G11 Ethernet Interface User Manual

Page 28

Advertising
background image

EtherNet/IP

22

3. Click the button with the three dots in the MSG instruction to bring up the MESSAGE

configuration window. Do the following settings:

Field Value

Description

Message Type

CIP Generic

CIP Message

Service Type

Get attribute single

CIP Service

Class

64

Fuji Vendor Specific Object

Instance 1

Instance

1

Attribute 23

M21 – DC link circuit voltage = Communication No.
35 = 23 hex

Destination DC_Voltage

Name of created destination tag

Path OPCG11SETN

Name of device. Click Browse and locate the module.
Must have been added as described in the IO
connection example chapter

When GetDcValue in the example is activated, DC voltage is read and stored in the DC_Voltage Tag.