GE Industrial Solutions AF-300 P11_G11 Ethernet Interface User Manual
Page 28
Advertising
EtherNet/IP
22
3. Click the button with the three dots in the MSG instruction to bring up the MESSAGE
configuration window. Do the following settings:
Field Value
Description
Message Type
CIP Generic
CIP Message
Service Type
Get attribute single
CIP Service
Class
64
Fuji Vendor Specific Object
Instance 1
Instance
1
Attribute 23
M21 – DC link circuit voltage = Communication No.
35 = 23 hex
Destination DC_Voltage
Name of created destination tag
Path OPCG11SETN
Name of device. Click Browse and locate the module.
Must have been added as described in the IO
connection example chapter
When GetDcValue in the example is activated, DC voltage is read and stored in the DC_Voltage Tag.