Appendix B - Drive Parameters

35

Data Format [12]: Index Data (ACC/DEC Time, Display Coefficient)

(MSB)

(LSB)

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Polarity

0 0 0

Index

portion

Data

portion

Field Description
Polarity

0: Positive

(+)

1: Negative

(-)

Index portion

0: 0.01 *

001–999

(0.00 – 9.99)

1: 0.1 *

100–999

(10.0 – 99.9)

2: 1

*

100–999

(100 – 999)

3: 10

*

100–999

(1000 – 9990)

Data portion

Value

Example) F07 (Acceleration time 1) = 20.0 s,

20.0 = 0.1 * 200 = 0400

H

+ 00C8

H

= 04C8

H

Data Format [14]: Operation Command

(MSB)

(LSB)

15 14

13 12

11 10 9 8 7 6 5 4 3 2 1 0

RST 0 0 0 0 X9 X8 X7 X6 X5 X4 X3 X2 X1 REV

FWD

(All bits are ON or active by 1)

Field Description
RST Alarm
X9-X1

Multi function command

REV

Reverse rotation command

FWD

Forward rotation command

Example) If M13 (Operation command, Final command) = FWD, X1, X5 = ON

0000 0000 0100 0101b = 0045H

Data Format [15]: Universal Output Terminal

(MSB)

(LSB)

15 14 13 12

11 10 9 8 7 6 5 4 3 2 1 0

0 0 0 0 0 0 0 0 0 0 0 Y5

Y4

Y3

Y2

Y1

Y5-Y1 = Universal command (All bits are ON by 1)

Example) If M15 (Universal output terminal) = Y1, Y5 = ON,

0000 0000 0001 0001

b

.= 0011

H