Modbus/tcp, Addressing, Commands – GE Industrial Solutions AF-300 P11_G11 Ethernet Interface User Manual

Page 23: Exception codes

Advertising
background image

Modbus/TCP

17

Modbus/TCP

This product incorporates a Modbus/TCP server according to version 1.0 of the Modbus/TCP specification.
The product listens for incoming connections on TCP port 502.

Up to 8 simultaneously connections can be set-up. A connection will be closed if no data has been exchanged
during 1 minute.

Addressing

This product supports the Modbus area for output/holding registers (4XXXX).

Register 40001-40255 corresponds to Communication No. 1-255.

Commands

The module supports the following Modbus/TCP commands:

Function
code

Function name

Description

3

Read multiple registers

Read one ore more registers in the drive

6

Write single register

Write to a single register

16

Write multiple registers

Write to multiple registers

23

Read/Write registers

Read and write to multiple registers with one command

Exception Codes

If a command cannot be executed an exception code is returned. The following exception codes can be

returned:

Exception
code

Exception name

Description

01

Illegal function

The function code in the query is not supported

02

Illegal data address

The data address in the query is outside the valid address
range or the address is invalid.

03

Illegal data value

This code will be returned if:
1. Trying to write to a read only register in the drive or
2. The requested register cannot be changed while the drive
is running.

06 Slave

device

busy

This code will be returned if:
1. The inverter is busy or
2. There is a communication error between the drive and the
communication adapter.