Fault detection and action – GE Industrial Solutions AF-300 P11_G11 Ethernet Interface User Manual
Page 19
Installation and Configuration
13
Fault Detection and Action
A network loss event will be generated to the drive from the Ethernet option board when any of the following
events occur:
Event
Source
Condition
Fault cleared when
Link lost
Hardware
Link was established.
Network cable connected
Connection time-out
-
Connection is deleted or
module receives information
on connection again.
Connection Idle
EtherNet/IP
Configured to set error
on IDLE. See drive
parameter o33.
Master is set in run mode
A consumed data exchange
enters the UNHEALTY
state.
EGD
The configured
consumption time must
not be set to zero.
Exchange enters the
HEALTHY state
The time from last
Modbus/TCP message has
exceeded the configured
Modbus time-out action.
Modus/TCP
Configured Modbus
timeout action must not
be set to zero.
See drive parameter
o34.
A new Modbus/TCP
message is received.
After an error is cleared, the error must be acknowledged to the drive before drive control will start again. The
drive’s reaction to a network loss event can be set, see the “Operation Configuration Parameters” section.