3. Safety

Safety Statements

Please read and follow all safety instructions and warnings before installing, maintaining,
or repairing the Lineage power system:

• The CE Mark demonstrates compliance with the European Union Council Directives

for Low Voltage and EMC.

• This system is Underwriters Laboratories (UL) Listed per Subject 1801, Power

Distribution Centers for Telecommunications Equipment (UL 60950-1).

• Install only in restricted access areas (dedicated equipment rooms, equipment closets,

or the like) in accordance with articles 110.27 of the U.S. National Electric Code
(NEC), ANSI/NFPA No. 70, and pursuant to applicable local codes.

• Not for use in a computer room as defined in the Standard for the Protection of

Electronic Computer/Data Processing Equipment, ANSI/NFPA 75.

o

Ne peut être utilisé dans une salle d’ordinateurs telle que définie dans la
norme ANSI/NFPA 75 Standard for Protection of Electronic Computer/Data
Processing Equipment

• This equipment is to be used in controlled environments (an area where the humidity

is maintained at levels that cannot cause condensation on the equipment, the
contaminating dust is controlled, and the steady-state ambient temperature is within
the range specified).

• This equipment has been evaluated for continuous use in ambient temperature from

-40°C to 45°C. Maximum 45°C ambient for plant outputs not exceeding 960A charge
and 1200A discharge, otherwise maximum 40°C ambient.

• This equipment must not be installed over combustible surfaces.
• For installations in the United States, Listed compression connectors are to be used to

terminate Listed field-wired conductors where required. For all installations, the
appropriate connector is to be applied only to the correct size conductor as specified
by the connector manufacturer, using only the connector manufacturer's
recommended tooling or tooling approved for that connector.

• If the proper connector for the country of installation is not provided, obtain

appropriate connectors and follow manufacturers and all local requirements for
proper connections. All national and local rules and regulations should be followed
when making field connections.

• The main output voltage (less than 60Vdc for all configurations) meets SELV

requirements. Loads connected between -48 volts and +24 volts are not SELV and
therefore shall not be connected.

• Insulation on field-wired conductors should be rated no less than 90° Celsius. Wire

conductor size should be sized per electrical codes for 75° Celsius wire, and based on
the ampacity of the associated protection device. Wiring internal to enclosed
equipment cabinets should be rated at 105° Celsius (minimum).