GE Industrial Solutions H2007001 G11 Series User Manual

Page 20

Advertising
background image

Infinity D Power System Installation Guide: +24V Systems

H2007001

Issue 2.0, June 4, 2009

20

DC DISTRIBUTION PANEL OVERCURRENT-PROTECTION DEVICE

CONFIGURATIONS

Circuit Breakers

Shelf(+)

Maximum

Amps(++),(+++)

Manufacturer Series Rating(+++++)

Comments

Airpax

LMLK,

LMLHPK

3-70A 1-pole

100A 2-pole
150A 2-pole
250A 3-pole

Cumulative adjacent
circuit breaker ratings
cannot exceed 250A.

QSGMT6

6 fuse holders –

57.6A total; 15A

rated fuse/position

R/C (QPQY2/8); uses
R/C fuse (JDYX2) by

SOC, Type AX1 or

AX1-B

J2007002

400 charge
500 discharge

Lineage Power

J2007002

L005

(++++)

3-70A 1-pole

100A 2-pole

Cumulative circuit

breaker ratings cannot

exceed 200A.

(+)

- Includes all List options.

(++)

- Maximum amps that the distribution section of the shelf is rated. Power supply output may be

rated less.

(+++)

- Plant ratings that exceed 640A charge and 800A discharge: top shelf adjacent to battery panel

shall not exceed 336A charge and 400A discharge.

(++++) - The J2007002 L051 shelf option is ten additional bullet-breaker positions located on right side

of shelf.

(+++++) - Plant ratings that exceed 640A charge and 800A discharge: top shelf adjacent to battery panel

shall not use either a 150A 2-pole or 250A 3-pole circuit breaker.


POWER SUPPLIES ALLOWED

IN H2007001 PO

WER DISTRIBUTION CENTER

Power Supply Model(#)

Type

Manufacturer Certification

NE075AC24 rectifier
NE030DC48 converter
NE100AC24 rectifier
NE050AC48 rectifier
NE075DC24 converter


Lineage Power


R/C (QQGQ2/QQGQ8)

(#) - May be provided with a non-safety affecting suffix.