Infinity D Power System Installation Guide: +24V Systems

H2007001

Issue 2.0, June 4, 2009

48

Install dc Bullet Style Circuit Breaker Modules for -48V Loads

This plant makes use of a [circuit breaker]/[lug landing] assembly for each normal format
bullet style circuit breaker. This section illustrates how these are installed.

CAUTION: Ensure Circuit Breakers are in the OFF position prior to installation.

CAUTION: In order to meet UL Listing temperature limits in the event of overload,
high current rated Bullet Breaker locations must meet all of these layout restrictions:
• Maximum rating of 1-pole breakers is 70A.
• Maximum rating of 2-pole breakers is 100A.
• Maximum grouping of 250 A before skipping a circuit breaker position.

Step

Action

1.

Open the Converter System Module door

2.

Locate Circuit Breaker (CB) mounting
panel.

Open door by pressing here