Infinity D Power System Installation Guide: +24V Systems

H2007001

Issue 2.0, June 4, 2009

13

• While installing batteries, follow all safety precautions outlined in the appropriate

battery product manuals.


• The intra-building port(s) of the equipment or subassembly is suitable for connection

to intrabuilding or unexposed wiring or cabling only. The intra-building port(s) of the
equipment or subassembly MUST NOT be metallically connected to interfaces that
connect to the OSP or its wiring. These interfaces are designed for use as intra-
building interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE,
Issue 4) and require isolation from the exposed OSP cabling. The addition of Primary
Protectors is not sufficient protection in order to connect these interfaces metallically
to OSP wiring. The Ethernet port is suitable for connection only to shielded intra-
building cabling grounded at both ends.