GE Industrial Solutions H2007001 G11 Series User Manual

Page 19

Advertising
background image

Infinity D Power System Installation Guide: +24V Systems

H2007001

Issue 2.0, June 4, 2009

19

UL Ratings as reflected in the UL Report in May 2009. Please note the available rectifier
output is reduced from the nameplate rating when converters are introduced to the system.


ELECTRICAL RATING:

Input (ac)

Output (dc)

Model

J2008001

Battery

Panel

V (50/60Hz)

Current

Vdc (++)

Max Current(+++)

Max Power

L001, L002,
L005, or
L006

640A charge
800A discharge

17,500 W

H2007001
Type A(+)

L003, L004,
L007, or
L008

200-240
(up to 28
feeds)

15 A draw 22 – 29

1280A charge
1600A discharge

34,985 W

Primary:
22 – 29

Primary:
640A charge
800A discharge

L001, L002,
L005, or
L006

200-240
(up to 28
feeds)

15 A draw

Secondary:
48 – 54.5

Secondary:
120A

17,500 W
maximum
combined
output

Primary:
22 – 29

Primary:
1280A charge
1600A discharge

H2007001
Type B(+)

L003, L004,
L007, or
L008

200-240
(up to 28
feeds)

15 A draw

Secondary:
48 – 54.5

Secondary:
120A

34,985 W
maximum
combined
output

L001, L002,
L005, or
L006

640A charge
800A discharge

34,880 W

H2007001
Type C(+)

L003, L004,
L007, or
L008

200-240
(up to 28
feeds)

15 A draw 44 – 57

1280A charge
1600A discharge

69,760 W

Primary:
44 – 57

Primary:
640A charge
800A discharge

L001, L002,
L005, or
L006

200-240
(up to 28
feeds)

15 A draw

Secondary:
24–27.25

Secondary:
300A

34,880 W
maximum
combined
output

Primary:
44 – 57

Primary:
1280A charge
1600A discharge

H2007001
Type D(+)

L003, L004,
L007, or
L008

200-240
(up to 28
feeds)

15 A draw

Secondary:
24–27.25

Secondary:
300A

69,760 W
maximum
combined
output


(+)

May be followed by –SD. When followed by –SD, the AC input will be up to 16 or 8 feeds rated:
(16)x 15 amps each feed or (8)x 30 amps each feed.

(++)

The marked output voltage may be any voltage range or specified voltage as long as it is within
the range specified in the electrical rating table.

(+++) Maximum 45°C ambient for output rating not exceeding 960A charge and 1200A discharge.

Otherwise, 40°C ambient. The secondary (converter) input is a load for the primary (rectifier)
output. This must be considered when loading the plant to its maximum rated primary output.