Install controller field wiring – GE Industrial Solutions H2007001 G11 Series User Manual
Page 66
Infinity D Power System Installation Guide: +24V Systems
H2007001
Issue 2.0, June 4, 2009
66
Install Controller Field Wiring
In addition to the temperature instrumentation, the controller has field connections for
Alarm Inputs, Alarm Outputs and a Local Area Network (LAN).
Step
Action
1.
Insert the terminated end of the Alarm Input wireset (CC848817651) into the Input Alarms
connector on the top edge of the controller.
2.
Insert the terminated end of the Office Alarm Output wireset (CC848817635 or similar) into the
Office Alarm connector on the top edge of the controller.
3.
Insert the terminated end of a 10/100Base-T CAT-5 LAN wireset into the LAN connector on the
top edge of the controller.
4.
Open the door to the widest position.
5.
Dress the field wiring using the tie points provided just behind the hinge to up and out the top of
the cabinet.
6.
Check to make sure the door can open and close without straining the connectors.