GE Industrial Solutions H2007001 G11 Series User Manual

Page 92

Advertising
background image

Infinity D Power System Installation Guide: +24V Systems

H2007001

Issue 2.0, June 4, 2009

92

Office Alarm Connector
All standard controller output alarm connections are available from the output connector. Connector J4
provides access to the primary customer alarm output interface. Connector J4 is a 20-pin right angle header
with latching capability. Standard color coded cable assemblies are available. Comcodes for the 50’ and
150’ input cables are CC848817635 and CC848817643, respectively. Contact technical field support for
additional cable options.

Pin #

(Wire Color)

Signal

Name

Twisted Pair

Pin #

(Wire Color)

Signal Name

NE843 Standard

Defaults

1

(BL)

PCR &

11

(W)

PCR_C

PCR

(Power Critical)

2

(O)

PMJ &

12

(W)

PMJ_C

PMJ

(Power Major)

3

(G)

PMN &

13

(W)

PMN_C

PMN

(Power Minor)

4

(BR)

UR1 &

14

(W)

UR1_C

BD

(Battery on Discharge)

5

(S)

UR2 &

15

(W)

UR2_C

VLV

(Very Low Voltage)

6

(BL)

UR3 &

16

(R)

UR3_C

FAJ

(External Fuse Major)

7

(O)

UR4 &

17

(R)

UR4_C

ACF

(ac Fail)

8

(G)

UR5 &

18

(R)

UR5_C

RFA

(Rectifier Fail)

9

(BR)

UR6 &

19

(R)

UR6_C

MRFA

(Multi Rectifier Fail)

10

(S)

UR7 &

20

(R)

UR7_C

HV

(High Voltage)

Note: Configuration jumpers for the alarm outputs have been set to provide an “Open” on alarm
from the factory. Alarm contact type can be changed – see Advanced Features User Guide.

Network (LAN) Connection (Optional)
The NE843 provides an Ethernet connection for a LAN and or Craft port connection. Connector LAN
provides a standard RJ45 shielded receptacle connection for a standard Cat-5 connection to the controller’s
10/100Base-T port. This port has two main modes of operation: Server mode, LAN mode (Static and
DCHP Client). In server mode the port can be used as a local Craft interface. In this mode, a local laptop
can be connected through LAN and its standard web browser used to directly access the controller by
typing in network address

http://192.168.2.1

. A connection should never be made between the controller

and LAN while the controller is in Server mode.

In Static or DHCP Client modes of operation the controller is supplied an IP address and other
network parameters and can be remotely monitored and accessed through the LAN. This is
generally a permanent connection between the controller and LAN so a Shielded Cat-5 cable is
suggested. Use appropriate routing techniques to connect the controller to the LAN.

Default Passwords are lineage, super-user and administrator.

Advertising