GE Industrial Solutions H2007001 G11 Series User Manual

Page 33

Advertising
background image

Infinity D Power System Installation Guide: +24V Systems

H2007001

Issue 2.0, June 4, 2009

33

Step

Action

9.

Insert the provided jumpers in the 4
locations where the dividers were removed.

10.

Torque each of the 8 jumper retention screws to 10 inch·lbs or 1.1 N·m.

11.

Insert each feed wire into the bottom of the
terminal block according to this diagram.
The jumper straps from the previous steps
assure that rectifiers 2 and 4 are powered:

R1

L1

R2

R3

L1

R4

R1

L2/European N

R2

R3

L2/ European N

R4

200-240Vac Wiring Diagram for 2 Wire + PE

Photo indicating positions 1 and 3 are powered .

12.

Strip 0.32 inches (8 mm) of insulation off the end of each AC wire.

13.

Make sure all strands are captured in the appropriate wire clamp.

14.

Torque each wire clamp to 5-7 inch·lbs or 0.6-0.8 N·m.

15.

Secure conduit fitting.

16.

Replace AC Termination door.

17.

Tighten Screws to 5-7 inch·lbs or 0.6-0.8 N·m.

Advertising