Rectifier/converter installation procedure, Rectifier/converter removal procedure – GE Industrial Solutions H2007001 G11 Series User Manual
Page 56
Infinity D Power System Installation Guide: +24V Systems
H2007001
Issue 2.0, June 4, 2009
56
Rectifier/Converter Installation Procedure
Step
Action
1.
Slide the rectifier/converter partially into a
slot.
2.
Open the faceplate by sliding the black latch
to the left to release the faceplate.
3.
Push the unit firmly into the shelf until seated.
Using optional air filter?
Yes – Proceed to Step 4.
No – Go to Step 5.
4.
Install an air filter by placing it inside the faceplate.
5.
Swing the faceplate closed until it is secured
by the latch.
6.
After 30 seconds, verify green LED and only green LED is on.
If this isn’t the case, see the Troubleshooting section.
Rectifier/Converter Removal Procedure
Step
Action
1.
Open the faceplate to disengage the
rectifier/converter.
2.
Remove the unit from the shelf.