ELECTRICAL CONNECTION

The compliance of the installation to relevant electrical codes

is the responsibility of the installer . Before carrying out any

electrical work, confirm that the main power supply is isolated .

The installer must ensure that the correct electrical drawing is

available .

Module Power Wiring

The power for each module should be taken from a customer

supplied, fused main power supply panel . It is further

recommended that the incoming power be supplied from a

properly sized disconnect switch . It is the responsibility of the

installer to provide adequate fusing or circuit breaker protection

for the incoming power to each module . Proper grounding of the

module is mandatory . A typical power wiring schematic is located

on page 63 - Power Distribution .

Module Control Wiring

After the power wiring has been run, the control wires can then

be connected . The wires should be carefully marked and installed

onto the terminals shown on the wiring diagram . External control

wires should be connected to the relevant terminals and devices .

All control wiring and external wiring to the sensors should not

be run in the same conduit as the power wiring .

Control Wiring Sizes and Lengths

When running control wires, proper gauged wires should be

used . The control wiring for the compressor contactors must be

in accordance with the minimum wire gage shown on the wiring

diagram . With 14 AWG the maximum distance allowed is 250

feet . With 16 AWG, 100 feet is acceptable . You should not exceed

50 feet when using 18 AWG . These lengths and gages are for the

use of 24 volt control circuits .

Electrical Phase Sequencing

Proper clockwise rotation for scroll compressor motors

is important to prevent damaging the compressors . If you

have access to a phase sequence indicating instrument it is

recommended to use this following the manufactures directions .

If not, you may “bump test” the compressors one at a time

with pressure gauges attached to the high and low gauge ports

of the compressors to check for proper rotation . Energize the

compressor for a few seconds to ensure the discharge pressure

gauge increases significantly . If the discharge pressure docs not

increase, proper rotation is reversed . You can quickly reverse

compressor rotation by opening the main electrical disconnect

and switching any two of the main power supply leads feeding

that compressor’s contactor .

Proper Voltage Balance

Occasionally, in three phase circuits, a voltage imbalance occurs

between phases . It is not recommended to operate equipment

when an imbalance greater than 2% occurs . This causes motors

to run at high temperatures and may affect their longevity . The

following example describes how to calculate the average voltage

of the three phases to see if the imbalance is greater than 2% .

Example: Line one = 226V; Line two = 230V; Line three = 228V

The average is: 226+230+228 = 228V

3

Next, 100 x (228-226) = 0 .9%

228

The voltage imbalance of the three phase circuit is 0 .9% . This is

well under the 2% range .

Checking

Before power is applied to the system, the wiring should he

visually inspected for loose connections or frayed terminal

connections . All control wiring should follow wiring instructions

supplied in the project submittal package .

Electrical Connection