Operational limitations – ClimaCool IOM AR2 SERIES User Manual

Page 48

Advertising
background image

46

www.climacoolcorp.com

®

VOLTAGE LIMITATIONS COMPRESSOR OPERATING LIMITATIONS

The following voltage limitations are absolute and operation

Maximum Compression Ratio ...................…. 9.5:1

beyond these limitations may cause serious damage

Maximum Operating Pressure Differential (PSI) …… 270

to the compressor.

Minimum Operating Pressuire Differential (PSI)…..…56

0

8

.

.

..

..

..

..

..

..

..

)

G

I

S

P

(

e

r

u

s

s

e

r

P

n

o

it

c

u

S

m

u

m

i

x

a

M

(

.

p

m

e

T

e

g

r

a

h

c

s

i

D

m

u

m

i

x

a

M

o

F) .................... 225

NOMINAL

VOLTAGE

MIN

VOLTAGE

MAX

VOLTAGE

Minimum Superheat At Compressor (

o

F) …......….... 10

208/230-3-60

187

253

Maximum Superheat At Compressor (

o

F) ...........….... 25

460-3-60

414

506

Oil Temperature (Max.) (

o

F) …………..…. 160

575-3-60

518

632

Maximum Sat. Discharge Temp. (

o

F) …………. 140

WATER FLOW DATA

AR2-25

AR2-30 AR2-50 AR2-65

Min. Evaporator Water Flow (GPM)

50

50 80 90

Max. Evaporator Water Flow (GPM)

100

100 180

210

Min. Lvg. Evap. Water Temp. (No Glycol; R-407C) (

o

F)

42

42 42 42

Min. Lvg. Evap. Water Temp. (No Glycol; R-22) (

o

F)

40

40 40 40

Min. Lvg. Evap. Water Temp. (With Glycol) (

o

F)

20

20 20 20

Max. Lvg. Evap. Water Temp. (

o

F)

50

50

50 50

Max. Lvg. Evap. Water Temp. (UniFlow) (

o

F)

55

55

55 55

Max. Evaporator Water Differential Temp. (

o

F)

15

15

15 15

Min. Evaporator Water Differential Temp. (

o

F)

7

7

7

8

NOTES:

1. All temperatures stated are for counterflow HX flow configuration unless “UniFlow” is specified.

EQUIPMENT ROOM AMBIENT LIMITATIONS

AR2-25

AR2-30 AR2-50 AR2-65

Minimum Equipment Room Temp.

(

o

F)

55

55 55 55

Maximum Equipment Room Temp.

(

o

F)

105

105 105

105

Operational Limitations