Application parameters, Performance multipliers & pressure drops – ClimaCool IOM AR2 SERIES User Manual

Page 43

Advertising
background image

41

www.climacoolcorp.com

®

Application Parameters

Performance Multipliers & Pressure Drops

Table AM-6

Performance Adjustment Factors vs. Altitude vs. Chiller Temperature Drop

Chiller

Sea Level

2000 ft.

4000 ft.

6000 ft.

Water Temp.

Capacity Flow, gpm kW Power Capacity Flow, gpm kW Power Capacity Flow, gpm kW Power Capacity Flow, gpm

kW

Drop (

o

F)

Multiplier Multiplier Multiplier Multiplier Multiplier Multiplier Multiplier Multiplier Multiplier Multiplier Multiplier Multiplier

8

0.995

1.246

0.998

0.99

1.244

1.003

0.986

1.238

1.006

0.98

1.232

1.012

10

1.000

1.000

1.000

0.993

0.997

1.004

0.989

0.99

1.007

0.983

0.996

1.014

12

1.005

0.834

1.001

0.996

0.831

1.004

0.992

0.826

1.008

0.986

0.821

1.016

14

1.010

0.716

1.001

0.998

0.714

1.005

0.994

0.709

1.009

0.989

0.704

1.018