Water treatment – ClimaCool IOM AR2 SERIES User Manual

Page 18

Advertising
background image

16

www.climacoolcorp.com

®

WATER CONTAINING

CONCENTRATION

Sulphate

Less Than 200 ppm

pH

7.0 – 9.0

Chlorides

Less Than 200 ppm

Nitrate

Less Than 100 ppm

Iron

Less Than 0.2 mg/l

Aluminum

Less Than 0.2 mg/l

Manganese

Less Than 0.1 mg/l

Dissolved Solids

Less Than 1000 mg/l

CaCO3 Hardness

30 – 500 ppm

CaCO3 Alkalinity

30 – 500 ppm

WATER TREATMENT

Proper water treatment is a specialized industry . We recommend

consulting an expert in this field to analyze the water for

compliance with the water quality parameters listed in Table 1

below . The material used in the ClimaCool chiller exposed to the

water are type 316 stainless steel, pure copper, and carbon steel .

Other materials may exist external to the ClimaCool chiller . It is

the users responsibility to ensure these materials are compatible

with the treated water . Failure to provide proper water quality

will void the ClimaCool module’s warranty . NOTE: For warranty,

proof of monthly water testing results showing compliance to

Table 1 Water Quality Parameters is required . Failure to provide

proper water quality will void the ClimaCool module’s warranty .

It is further recommended to seek an experts advice to specify

the appropriate water treatment required . Typical additives to

hydronic systems include rust inhibitors, scaling preventative,

antimicrobial growth agents, and algae preventatives . Anti-freeze

solutions may also be used to lower the freezing point .

Heavily-Contaminated Water

In such instances whereby the particulates in the water are

excessive it is recommended to install an intermediate plate &

frame heat exchanger to isolate the ClimaCool chiller from the

building water system .

Other Considerations

The following considerations are listed to help achieve system

longevity .

Cooling Tower

The cooling tower should be located away from sources of

external contaminates such as trees, dust, or grass cuttings . Insect

infiltration can be reduced by eliminating lights near the tower .

A periodic visual inspection of the tower system should be made

and contaminates removed as required .

Table 1 - Water Quality Parameters

Water Treatment