Automatic timer flush package – ClimaCool IOM AR2 SERIES User Manual

Page 23

Advertising
background image

21

www.climacoolcorp.com

®

SAFETY FIRST!

Keep fingers away from valve opening to avoid getting

caught in the moving parts . The electric motor supplies a

sufficient amount of power to cause personal injury . Take

precaution when handling .

Automatic Timer Flush ATF-EA-1 .5 (optional)

Valve Specifications

A . Water-resistant Polypropylene Motor Case

B . High Torque Motors with Perma-lube Gears

C . Open & Close Indicator

D . Stainless Steel Ball Valve & Hardware

E . Auto Reset Circuit Breaker

F . 90 Degree Bidirectional Rotation

G . Controller Case

Fig . 3

TROUBLESHOOTING: If you require further assistance, please call us at (405) 745-3185.

PROBLEM

POSSIBLE CAUSE

SOLUTION

• Valve is leaking past ball

• Seals damaged or worn out

• Install repair kit

• Valve is not stopping at proper

• Adjust limit switches

closed position

• Valve stem leaks

• Worn stem seals

• On metal valves: tighten stem packing

nut 1/2 turn .

CAUTION! Over tightening stem nut

could cause drag on motor and trip

internal circuit breaker. May require

repair kit or new valve.

• Valve body leaks

• Loose body bolts or excessive operating

• Check bolts and observe recommended

pressure

ratings

• Defective seals

• Install repair kits or new valve

• Valve hard to turn

• Swollen seals or product buildup in valve

• Check valve for compatibility with

chamber

product, may require valve cleaning or

new valve

• Valve bolts too tight

• Loosen bolts slightly

• Stem nut too tight

• Loosen stem nut slightly

Automatic Timer Flush Package