BOLTED LID MODELS: ClimaCool Strainer models CS-4B,

CS-6, CS-8, and CS-10 have “bolted” lid designs . Grade 5 zinc-

plated bolts, nuts, and washers are used to attach the lids to these

strainers . See Table 1 for the proper lid bolt size and torque rating

for each strainer . (Exercise care when tightening the lid bolts so

as not to damage the strainer lid or housing) .

It is important to follow the torque specifications as

overtightening may result in premature failure of the bolts . It

is equally important to follow a star wheel torque pattern when

tightening the lid bolts (see Fig . 2) . The strainer lid may not be

seated down completely after the first torque sequence (this is

especially evident on the larger strainers such as the CS-8 and

larger) . A second torque sequence should be adequate to seat the

lid securely to the body .

Strainer Operation

Periodically, it will be necessary to flush out the debris that is

collected and settles to the bottom of the strainer reservoir . The

larger ClimaCool strainers (CS-4, CS-6, CS-8, and CS-10) are

equipped with a flush port (or drainage port) extending inside the

strainer . When it becomes time to clean the strainer, the flush port

valve should be opened while the strainer is in operation (while

pressurized and with water flowing) . A thorough flushing of the

strainer reservoir will depend upon the length of time the flush

valve remains opened . This flush time will typically range from

15 to 60 seconds depending on the flow, inlet water pressure,

and the amount of debris collected by the strainer . As a general

rule, the larger strainers will require higher inlet water pressures

in order to achieve a complete flushing . For example, the CS-4

model can be flushed with inlet water pressures as low as 15 PSI,

while the CS-6 can be flushed with 30 PSI . The CS-8 and CS-10

models should be flushed with inlet water pressures greater than

40 PSI . Strainer

Note: When shutting down the chiller for extended periods of

time, the strainer should be isolated and completely drained .

Strainer Element Cleaning

If your strainer assembly is equipped with optional pressure

gauges, you will be able to monitor the pressure differential

between the inlet and outlet sides of the strainer . Under a normal

“clean” strainer operation this pressure difference should be

slightly under 1 PSI . When this pressure differential reaches 5-10

PSI, the strainer element may require cleaning .

CAUTION: PRIOR TO DISMANTLING THE STRAINER

FOR CLEANING, IT IS IMPERATIVE THAT THE STRAINER

ASSEMBLY IS ISOLATED AND COMPLETELY DE-

PRESSURIZED . Follow these steps when cleaning the

ClimaCool Strainer element:

Step 1 (Bolted Lid Models): Remove the top of the ClimaCool

Strainer by removing the Grade 5 Zinc plated bolts from the lid .

Step 1 (Band-Clamp Lid Models): Remove the top of the

ClimaCool Strainer by taking off the band-clamp assembly .*

Step 2: Lift the strainer element (conical screen) out of the

strainer body .

Step 3: Carefully scrub down the strainer element with a rigid

nylon brush until all matter is loosened . DO NOT USE STEEL

BRUSH

Step 4: Wash the strainer element off with clean water . It is

preferable to use a hose with a significant amount of water

pressure . DO NOT USE A PRESSURE WASHER .

Strainer

STRAINER

BOLT SIZE

RECOMMENDED TORQUE

CS-2 (Clamp)

5/16 - 18

40 - 50 in . lbs .

CS-3 (Clamp)

5/16 - 18

60 - 80 in . lbs .

CS-4C (Clamp)

5/16 - 18

75 - 85 in . lbs .

CS-4B

3/8 -16

15 - 25 ft . lbs .

CS-6

1/2 - 13

45 - 55 ft . lbs .

CS-8

1/2 - 13

45 - 55 ft . lbs .

CS-10

5/8 - 11

80 - 100 ft . lbs .

Fig . 2 - Recommended

Torquing Sequence

Table 1