Head pressure control valve operation ori/ord, Table 1 table 2, Table 3 – ClimaCool IOM AR2 SERIES User Manual

Page 57

Advertising
background image

55

www.climacoolcorp.com

®

Head Pressure Control Valve Operation ORI/ORD

EXAMPLE: Our example calls for a compressor equipped with

unloaders . Since the compressor would unload at the low ambients

this must be taken into consideration . This is necessary since as the

compressor unloads, the condenser’s capacity increases and additional

flooding is required . Using the same roof-top unit as in the earlier

example (40°F evaporator and minus 20°F minimum ambient), a

multiplier of .79 is shown in Table-2 . And since we have unloaders

(50%), this .79 is used to enter Table-3 to find a multiplier of .91 . This

final multiplier is applied to the 119 pounds calculated earlier to arrive

at the final extra charge requirement: 119 x .91 = 108 pounds . This is

added to the normal system charge to arrive at a total system charge .

Table 1

Table 2

Percent of Condenser to be

Flooded

High Suction Temp.

A/C Chillers

Evaporating Temperature

o

F

Condenser

Ambient

Temperature

o

F

35

40

45

50

80

0

0

0

0

70

0

0

0

0

60

26

20

10

4

50

45

40

33

28

40

56

52

46

42

30

64

60

55

51

20

69

66

62

59

0

76

73

70

68

-20

80

79

76

73

Table 3

Condenser Flooding

with NO Unloading

Percent of Full

Compressor

Capacity

= 50%

0

5

5

0

3

5

0

1

7

5

5

1

0

6

0

2

3

6

5

2

6

6

0

3

9

6

5

3

2

7

0

4

4

7

5

4

6

7

0

5

9

7

5

5

1

8

0

6

3

8

5

6

6

8

0

7

8

8

5

7

1

9

9

7

*

2

9

0

8

6

9

5

8

Advertising