Filling the water system – ClimaCool IOM AR2 SERIES User Manual

Page 17

Advertising
background image

15

www.climacoolcorp.com

®

Filling The Water System

FILLING THE WATER SYSTEMS

It is imperative that the water systems are free from debris

prior to initial operation . See the Water Treatment section for a

comprehensive list of precautions .

Filling, Purging and Leak Testing the System

After the water systems have been properly installed a visual

inspection should be made to all joints for tightness . If the chiller

is to be installed in an existing system, the cleanliness of the

existing system can be judged from the operating conditions of

the present machines . The cooling tower in particular, should be

inspected and cleaned if required . It is a good practice to at least

flush the existing system and ideally, to acid wash the system

before connecting a new chiller .

We recommend the following sequence to fill and leak check the

water systems:

1 . Close all isolation valves inside each modular chiller .

2 . Ensure that all drain valves are closed and that all water main

isolation valves are opened .

3 . The system should be filled with clean water send through a

strainer and the system checked for leaks .

4 . Once the main water lines and the chiller headers are filled

with clean water, purge and repeat the filling process several

times .

5 . Open the isolation valves inside each modular chiller and

repeat the filling process, this time also checking for leaks

inside each module .

6 . Following the final filling and leak checking procedure, air

should be purged from the system .

Cleaning the System

We recommend the following sequence to properly clean the

water systems:

1 . If possible, install a temporary bypass line between the supply

and return water lines of both water systems prior to cleaning

the system .

2 . Close all isolation valves inside each modular chiller before

engaging the main water pumps .

3 . The pumps should be run with the strainer in place (see the

Starting the Pumps section for proper pump startup) . All

external hydronic branches should be open to all devices in

the system .

4 . After several hours of operation, the strainer should be

isolated and cleaned .

5 . Step 4 should be repeated until there is no more debris being

collected by the strainer .

6 . Finally, open all isolation valves inside each modular chiller

and repeat step 4 and 5 .

If it is not possible to install the bypass line in step 1 above, it is

recommended to drain out the initial fill of water to help flush out

debris . The chiller isolating valves should be closed to prevent

debris from being washed into the chiller as the water drains out .

Before refilling and purging the system again, the strainers should

be removed and cleaned . This action should be repeated until

there is no more debris being collected by the strainer .

Starting the Pumps

Follow manufacturer’s recommendations when starting the

pumps for the first time . The system should be checked for leaks

and air purged with the pumps in operation . The pressure drop

across the heat exchangers will give a good indication of flow

through the system (see page 35) . This should be immediately

checked against the expected pressure drop for the flow rate

required . If the pressure drop begins to fall and the flow rate is

falling, this could indicate the need to clean the strainers .

Advertising