Strainer – ClimaCool IOM AR2 SERIES User Manual

Page 21

Advertising
background image

19

www.climacoolcorp.com

®

Step 5: Wash all matter from the strainer gaskets and clean the

inner-ring where the bottom of the strainer element rests .

Step 6: Make sure the U-shaped gasket is fitted securely to the

bottom of the strainer element . Reposition the strainer element

into the body of the strainer .

Step 7: Make sure the strainer head gasket is secure on the top of

the strainer body . On V-Band models, O-rings should be seated

completely in the body flange . Reposition the strainer lid back on

the strainer body . Tighten the lid securely either with the bolts or

with the band-clamp .

• For band-clamp models, opening and closing is achieved

without adjusting the lock nut . It is tightened at the factory

to the correct compression . (Minor tightening may be

necessary if the gasket loses memory over time .) To open the

clamp, depress the safety latch and pull the over-center lever

outward . To close the clamp, make sure the T-Bolt is seated

in its receiver and push the overcenter lever back toward

the strainer housing . Be sure that the safety latch is engaged

before putting the module to use .

What Is Water Hammer?

Water hammer is a phenomenon that can occur in fluid systems

with long pipes . Water hammer is a rapid change of pressure

caused by a rapid change in velocity . If the flow has been

abruptly shut off downstream, the pressure in the entire system is

raised very quickly .

What Causes Water Hammer?

Any action that can cause a rapid change in the velocity of the

flow can set off a water hammer, such as closing a downstream

valve, pump stoppage, etc . Typically, for short lengths of pipe

(below 500 ft), downstream valves that are closed within 1/10th

of a second can generate a water hammer .

What Can Water Hammer Do?

Pressure spikes from water hammer can raise fluid pressures to

dangerously high values . These pressure spikes can cause serious

damage to valves, pipes, strainers, joints, etc . The ClimaCool

Strainer is rated to an absolute maximum pressure of 150 PSI

for bolted lid models, and 125 PSI for band clamp lid models .

A water hammer pressure spike that raises the pressure higher

than the maximum rated pressure may result in strainer damage,

voiding the manufacturer’s warranty .

What Can I Do To Prevent Water Hammer?

There are certain precautions that can be taken to prevent or

decrease the effect of water hammer . The addition of a surge

tank or accumulator fitted with a suitable pressure relief valve

and strategically located within the water system may provide

adequate protection against the effects from water hammer .

Careful attention should be given to the design and control

strategy for valves and pumps so their actions do not invite a

water hammer .

Strainer