Head pressure control valve operation ori/ord – ClimaCool IOM AR2 SERIES User Manual

Page 55

Advertising
background image

53

www.climacoolcorp.com

®

The ORD opens after the ORI has offered enough restriction to cause the

differential between condensing pressure and receiver pressure to exceed

20 psi . The hot gas flowing through the ORD serves to heat up the cold

liquid being passed by the ORI . Thus the liquid reaches the receiver

warm and with sufficient pressure to assure proper expansion valve

operation . As long as sufficient refrigerant charge is in the system, the

two valves modulate the flow automatically to maintain proper receiver

pressure regardless of outside ambient .

PROPER SELECTION OF HPC VALVES — To ensure proper

performance, head pressure control valves must be selected and applied

correctly . This is covered thoroughly in Bulletin 90-30 . However, proper

installation procedures are equally important .

VALVE LOCATION/PIPING SUGGESTIONS — The ORI and

ORD valves can be installed in horizontal or vertical lines, whichever

best suits the application, and permits easy accessibility of all valves .

Consideration should be given to locating these valves so they do not

act as an oil trap and so solder cannot run into the internal parts during

brazing . Precautions should also be taken to install the valves with the

flow in the proper direction . The ORI valve CANNOT be installed in

the discharge line for any reason.

Figure 4 is a piping schematic only to illustrate the general location

of the ORI, and ORD valves in the system . ClimaCool recommends

that recognized piping references be consulted for assistance in piping

procedures . ClimaCool is not responsible for system design, or for

misapplication of its products . If these valves are applied in any manner

other than described in this bulletin, the ClimaCool warranty is void .

The inlet connections on the ORI-10 valves should be sized the same as

the outlet of the condenser where possible . The ORD-4 is available with

5/8” ODF and 7/8” ODF solder connections . On systems with discharge

lines smaller than 5/8” OD, the bypass line can be the same size as the

discharge line and the ORD-4 connections can be bushed down . If the

system capacity is greater than any of the head pressure control valves

ratings, these valves can be applied in parallel .

VALVE STRAINERS – Catch-All

®

filter-driers – See·All

®

moisture

and liquid indicator — Just as with any refrigerant flow control device,

the need for an inlet strainer is a function of system cleanliness and

proper installation procedures . When the strainer is used with the ORI,

the tubing is inserted in the valve connection until the tubing and strainer

flange ring are up against the tubing stop, thus locking the strainer in

place . See Below:

BRAZING PROCEDURES — Any of the commonly used brazing

alloys for high side usage are satisfactory . However, when soldering

or brazing, it is very important that the internal parts be protected by

wrapping the valve with a WET cloth to keep the body temperature

below 250°F for the ORI; and, 300°F for the ORD-4 . Also, when using

high temperature solders, the torch tip should be large enough to avoid

prolonged heating of the copper connections . And, always direct the

flame away from the valve body .

TEST and OPERATING PRESSURES — Excessive leak testing or

operating pressures may damage these valves and reduce the life of the

operating members . For leak detection an inert dry gas, such as nitrogen

or CO2, may be added to an idle system to supplement the refrigerant

pressure .

CAUTION: Inert gases must be added to the system carefully through

a pressure regulator. Unregulated gas pressure can seriously damage

the system and endanger human life. Never use oxygen or explosive

gases.

The table below lists the maximum values each valve can withstand

without damage . Precautions must be taken to keep test or operating

pressures below these values .

VALVE SETTINGS and ADJUSTMENT — A complete discussion

on pressure settings is given in the Application Section of Bulletin 90-30 .

To determine the proper setting or a specific system, that section should

be reviewed .

Type Valve

Maximum

Pressure

Rated

PSIG

ORI-10 65/225 H

450

0

5

4

4

-

D

R

O

Head Pressure Control Valve Operation ORI/ORD

Advertising