Automatic Timer Flush (AFT) Package

The ATF-EA-1 .5 flush valve package provides an automatic

method for flushing away the debris collected In the strainer’s

reservoir . The power supply and timer controls for the valve

package are housed inside the ATF control box . The ATF controls

can be preprogrammed to set the flushing duration and the time

interval between flushes .

System Components:

A . Timer Based Valve Controller (see Fig . 1) sets the flush

duration (length of the flush) and the flush interval (time

between flushes) .

B . Electric Ball Valve: designed for dirty water use (see Fig .

1 & 2) .

Fig . 1

A

GREEN POINTER

INNER RING

(LENGTH OF FLUSH)

(FACTORY SET AT

8-SECONDS)

RED POINTER

OUTER RING

(TIME BETWEEN

FLUSHES)

(FACTORY SET AT

24-HOURS)

Fig . 2

B

[email protected] POWER

FROM PDA OR 120V PLUG

IN TRANSFORMER

OPEN/CLOSE

INDICATOR

COVER-PLATE SCREWS

(4) IN CORNERS OF BOX

(TIMER BASED VALVE

CONTROLLER)

CONTROL SWITCH

Automatic Timer Flush Package

Operation Instructions:

Flush valve line must be piped to atmospheric pressure such as an

open floor drain . The flush line should not undergo any changes

in elevation and should be sloped downward in the direction of

drainage . DO NOT PIPE THE FLUSH OR DRAIN LINE INTO

A PRESSURIZED LINE .

Note: The Automatic Timer Flush Package Needs To Be

Programmed When It Is Received By The End-user . The

programming is simple and takes only a few moments . However,

because every application has different parameters that affect the

required frequency between flushes and the duration of the flush,

the end-user must choose the controller’s settings (refer to your

specific strainer manual) .

To program the ATF Controller:

Plug the transformer into a 120-VAC outlet . Insert the 12-VDC

plug coming from the transformer into the jack on the underside

of the ATF box . Test for power by pressing the manual flush side

of the control switch (lower switch light should come on and the

valve will start to open) . Adjust the “ON-TIME” (Valve Open)

by turning the inner timer ring with the GREEN POINTER

clockwise to increase duration . (“ON-TIME” RANGE, See Fig .

1) Adjust the “OFF-TIME” (Valve Close) by turning the outer

ring with the RED POINTER clockwise to increase duration .

(“OFF-TIME” RANGE, See Fig . 1) Set the control switch to auto

flush . The red off light on the timer will come on and the upper

light on the switch will come on and stay on . During the flush

cycle the on light on the timer and the lower switch light will

come on .

Control Switch: (see illustration)

Control switch flushing is initiated by pressing and holding

down the manual control switch located on the front of the

controller . The manual flush control switch can also be used to

conveniently drain the water out of the strainer before removing

the conical screen element from the strainer housing . A yellow

indicator arrow on top of the ATF Valve will rotate in sync

with the ball valve to show the valve position (open or closed) .

When the manual flush control switch is released, the valve will

automatically close .\