ClimaCool Water Piping Configurations

The ClimaCool Modular Chiller -
Water Piping Configurations

Field Piping Direct Return - Optional for 1-5 Modules (Figure 1)

Field Piping Reverse Return (Preferred for 1 to 5 Modules) Required for 6 to 7 Modules (Figure 2)

Unit 1

Unit 2

Unit 3

Unit 5

Unit 4

Blank Off

Plates

60” Sensor Location

(Field-Installed)

PressureTaps

with Shutoff Valves

& Gauges

Flow Out

Flow Switch

Isolation Valve

Thermometer Well

Thermometer Well

PressureTap

w/Shutoff

Valve &

Gauge

Isolation Valves

Strainer

Pump

Flow In

Blank Off

Plate

Blank Off

Plate

60” Sensor Location

(Field-Installed)

7

ti

n

U

3

t

i

n

U

2

t

i

n

U

1

t

i

n

U

Unit 6

Unit 5

Unit 4

Thermometer Well

PressureTap

w/Shutoff

Valve &

Gauge

Isolation Valves

Strainer

Pump

Flow In

Flow Out

Thermometer Well

Flow Switch

Isolation Valves

Pressure Taps

with Shutoff Valves

& Gauges

NOTES:

1 . Figures 1 and 2 are required piping for proper water regulation and distribution through ClimaCool modular chillers .

2 . Module order and incoming/outgoing water flow as shown in both Figure 1 and 2 can be set up as either a left-to-right or right-to-

left configuration .

3 . Condenser Hydronic Circuit shown . Piping configurations are similar for the chilled water hydronic circuit .

4 . For condenser and chilled water (evaporator) inlet/outlet location dimensions, refer to Module Dimensional Data .

5 . A flow switch (supplied by others) is a required safety device for ClimaCool modular chillers on the chilled and condenser water

circuits .

6 . Maximum water flow rates for both evaporator and condenser water header systems in one bank of modules is 1000 GPM . Field

Piping Reverse Return - (Preferred 1 to 5 modules) Required for 6 to 7 Modules (Figure 2)

7 . The chilled water piping on each module is pre-insulated at the factory with ¾” closed cell foam rubber . Insulation (3/4”) on the

chilled water header connection flanges is to be applied in the field by the installer, after the modules are bolted together on site .