Chiller operation and maintenance – ClimaCool IOM AR2 SERIES User Manual

Page 60

Advertising
background image

58

www.climacoolcorp.com

®

CHILLER OPERATION AND MAINTENANCE
Pressure and Temperature Log

A log of temperatures and pressures should be taken regularly .

Periodically conduct a visual inspection of the chiller to identify

problems before they reach the point of failure . As with any

mechanical system, it is necessary to conduct a series of checks to the

ClimaCool chiller to confirm correct operation .

HEAT EXCHANGERS
Back Washing

It may become evident from the recorded daily log data that the

performance of the chiller is gradually degrading . This could be

due to a buildup of debris or sludge obstructing the free passage of

flow through the heat exchangers . This debris can be removed by a

“back washing” process, which involves the introduction of a forced,

violent, backwards flow through the heat exchanger, using a carefully

formulated flushing solution . To be effective, this back flow should

be slightly higher than the normal flow, and, in the opposite direction .

The difficulties and practicality of this method depends on the back

wash pumping system itself . Another method would be to back flush

each heat exchanger using city water as opposed to system water

(see Fig . 1 page 59, City Water Cleaning Arrangement) . Note: Check

city water pressure meets requirements for back washing . The back

washing procedure is accomplished by isolating each individual heat

exchanger, and introducing the city water using a connection hose

to the 3/4” service port to flow in an opposite direction from the

“normal” heat exchanger flow direction . On the opposite 3/4” service

port, connect a drain hose to run to a suitable floor drain . Continue

back flow until all debris is removed .

Chemical in Place Washing

“Chemical Clean In-Place Washing” will typically provide the best

debris removal, even from severely clogged heat exchangers . It is

only necessary to mechanically and electrically isolate one chiller

module at a time which undergoes the “Clean In-Place Washing” .

The rest of the chiller modules can continue to operate to satisfy the

cooling load required . The cleaning tank, pump and pump strainer

should be arranged in the manner shown in Fig . 2 page 59, In Place

Cleaning Arrangement . The flow of the cleaning is arranged in the

opposite flow to the normal operational direction . Connection points

are provided using the 3/4” service ports at each heat exchanger .

The cleaning solution used can be either a detergent or hot water to

remove particles and simple cleaning . If correct water treatment has

been implemented this should provide adequate cleaning for most

situations . The solution can be pumped through the heat exchangers

and allowed to “soak” for a time and then pumped again .

If it is required to remove carbonates, then an acidic wash should be

used . A 2% solution of phosphoric or sulfamic acids in pure water are

generally acceptable . These acid solutions should only be allowed

to circulate within the heat exchanger for 10 to 15 minutes, followed

by a thorough pure water flush for 10 to 15 minutes . Hydrochloric or

sulfuric acids must not be used . In any case, you should consult the

chemical supplier to establish the correct formulation and handling

process . The materials, which will be exposed to the wash, are stated

on page 16 - Water Treatment .

Once the washing is complete, the solution should be flushed out

completely by pumping clean, fresh water through the chiller . To

achieve a reasonable level of dilution, it may be required to change

the water several times . After cleaning, the water quality and water

treatment should be confirmed .

If you have questions related to the suitability of a solution, please

contact ClimaCool for more information .

Chiller Operation and Maintenance

Advertising