Object 1800h: 1, Transmit pdo communication, Parameter – BEI Sensors THK4 User Manual

Page 26: Object 1801h: 2

Advertising
background image

www.beisensors.com

page

26/57

Object 1800h: 1

st

Transmit PDO Communication Parameter

This object contains the communication parameter of the 1

st

transmit PDO.

Subindex Description

Data Type

Default Value

Access

Restore after

BootUp

0

Number of sub indices

Unsigned 8

5

ro

yes

1

COB-ID

Unsigned 32

180h + Node ID

rw

yes

2 Transmission

Mode Unsigned

8

FE

rw

yes

3

Inhibit Time

Unsigned 32

0

rw

yes

4 Not

available

5

Event Timer

Unsigned 32

64h or 0

rw

yes

Object 1801h: 2

nd

Transmit PDO Communication Parameter

This object contains the communication parameter of the 2

nd

transmit PDO. NOTE: In the OCD versions

C2 and C5 the second PDO was configured via object 1802!

Subindex Description

Data Type

Default Value

Access

Restore after

BootUp

0

Number of sub indices

Unsigned 8

5

ro

yes

1

COB-ID

Unsigned 32

280h + Node ID

rw

yes

2 Transmission

Mode Unsigned

8

1

rw

yes

3

Inhibit Time

Unsigned 32

0

rw

yes

4 Not

available

5 Event

Timer

Unsigned

32

0

rw

yes

Transmission Mode

The transmission mode can be configured as described below:

Transmission Mode

Transfer

Value

(decimal)

Cyclic

Acyclic

Synchro

nous

Asynchr

onous

RTR

only

Notes

0

X X

Send PDO on first Sync message

following an event

1-240

X

X

Send PDO every x Sync messages

241-251 reserved