Object 6000h: Operating parameters

This object shall indicate the functions for code sequence, commissioning diagnostic control

and scaling function control.

Code sequence: The code sequence defines, whether increasing or decreasing position values are output,

in case the encoder shaft rotates clockwise or counter clockwise as seen from the point of view of the

shaft.

Scaling function control: With the scaling function the encoder numerical value is converted in software to

change the physical resolution of the encoder. The measuring units per revolution (object 6001h) and total

measuring range in measuring units (object 6002h) are the scaling parameters. The scaling function bit is

set in the operating parameters. If the scaling function bit is set to zero, the scaling function is disabled.

Bit structure for the operating parameters

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Use MS MS MS MS R

R

R

R

R

R

R

R

MD SFC CD CS

Table Description:

MS:

Manufacturer Specific Function (not available)

R:

Reserved for future use

MD:

Measuring direction (not available)

SFC:

Scaling function (0 = disable, 1 = enable)

CD: Commissioning

diagnostic

control (not availabe)

CS:

Code sequence (0 = CW Up, 1 = CCW Up)

Code Sequence (CS Bit 0) is hardwired to Code Sequence (CS Bit 0) in object 2100h.

Subindex Description

Data Type

Default Value

Access

Restore after

BootUp

0h

Operating Parameter

Unsigned 16

1h

rw

yes