6. Diagnosis

6.2 Troubleshooting

6.2.1 Power on – Encoder doesn’t respond

Problem:

The bus is active but the installed encoder

transmitted no boot up message.

Possible solution:

-

The encoders have the default baud rate

20kbaud. Adapt your PLC setting

accordingly.

-

Reprogram the encoders baud rate

-

Restart encoder so the new baud rate

setting will be valid.

6.2.2 Malfunction of the position value during

transmission

Problem:

During the transmission of the position value

occasional malfunction occurs. The CAN bus can

be temporary in the bus off state also.

Possible solution:

Check, if the last bus node has switched on the

terminal resistor.

6.2.3 Too much ERROR-Frames

Problem:

The bus load is too high in case of too much error

frames.

Possible solution:

Check if all bus node has the same baud rate. If

one node has another baud rate error frames are

produced automatically.

6.2.4 Limit switches without function

Problem:

The encoder didn’t transmit the bits for the limit

switches.

Possible solution:

The limit switch functionality has to be activated

once. Please follow the description you can find at

4.5.

6.2.5 Baudrate and Node Number changes

Notice: The changing of baud rate and node

number are only valid after a new power up, NMT

Reset or the store parameters command.