Object 1a01h: 2nd transmit pdo mapping parameter, Object 1f50h: download program area, Object 1f51h: program control – BEI Sensors THK4 User Manual

Page 28: Object 1a01h: 2, Transmit pdo mapping, Parameter

Advertising
background image

www.beisensors.com

page

28/57

Object 1A01h: 2

nd

Transmit PDO Mapping Parameter

This object contains the mapping parameter of the 2

nd

transmit PDO.

Subindex Description

Data Type

Default Value

Access

Restore after

BootUp

0

Number of sub indices

Unsigned 8

2

ro

yes

1 2

nd

mapped object

Unsigned 32

60040020h

rw

yes

Object 1F50h: Download Program Area

This is a special object that has functionality for the bootloader feature. (see Bootloader chapter)

Use this entry to download your Intel hex file with the programming data. Detailed information about

Domain download and Block transfer in CiA Draft Standard 301 Application Layer and communication

Profile.

Subindex Description

Data Type

Default Value

Access

Restore after

BootUp

0h

Number of sub indices

Unsigned 8

2h

ro

Yes

1h

DOMAIN

wo

yes

Object 1F51h: Program Control

This is a special bootloader object, to update the firmware (see Bootloader chapter).

This array controls the programs residing at index 0x1F50.

Subindex Description

Data Type

Default Value

Access

Restore after

BootUp

0h

Number of program control

entries

Unsigned 8

2h

ro yes

1h

Unsigned

32

rw

yes

Sub-index 1h and higher control the memory block functionality. They can have the following values:

for writing:

1 - start downloaded program

4 - erase flash

Advertising