CONFIGURATION 

Step Five 

This section will take you through the key steps in the setup and configuration of the EchoSwitch®: 

1) Select the units for configuration. 

a. Determine the measurement units that will be used to configure the sensor. 

2) Measure the distance from the bottom of the tank (empty level) to the bottom of the sensor. 

a. Be sure to include the added height of installation fittings. 

3) Measure the distance from the bottom of the tank (empty level) to the full level of liquid. 

a. Take into account the dead band of the sensor. 

4) Determine how many relays you will use and what each of their functions will be. 

a. Example: relay will fill a tank with a pump and relay 2 will provide a high alarm. 

5) Measure  the  distances  from  the  bottom  of  the tank  (empty  level)  to  the  positions  for  all  of  the  relay 

functions.  

a. Pump  and  Valve  functions  will  have  typically  have  two  set  points,  the  level  where  the  pump 

turns on and where it turns off or the level where the valve opens and closes. 

How to enter the TOP‐LEVEL MENU 

1. Press  and  hold  SELECT  (approximately  5  seconds) 

until PROG is displayed. 

2. The  TOP‐LEVEL  MENU  items  will  rotate  through 

display. 

3. Use SELECT to choose a MENU item. 

How to exit the TOP‐LEVEL MENU 
In TOP‐LEVEL MENU, press SELECT when RUN appears. 

How to configure UNITS 

1. In the TOP‐LEVEL MENU mode, press select when  

2. Press  SELECT  to  choose  between  INCHES,  CM 

(centimeter), FEET, METERS or PERCENT. 

3. Select EXIT to return to the TOP‐LEVEL MENU. 

Note:  Reading the level of liquid in Percent 

 Flowline recommends that when selecting PERCENT, 

configure  the  Height  and  Fill_H  settings  before 
selecting PERCENT in order to span the EchoSwitch® 
for your application requirements. 

 When  in  PERCENT,  the  operational  span  will  be 

based  upon  the  last  TANK  settings,  100%  will  occur 
at the Fill‐H level and 0 percent at the bottom of the 
tank. 

 When  PERCENT  is  selected,  the  TANK  settings 

(Height and Fill_H) will be disabled.  

 

 

 