CONFIGURATION (cont.) 

Step Five 

How to Duplex two relays:  Duplex enables EchoSwitch® to use two relays to alternate after each cycle while 
performing a lead‐lag operation.  To begin, configure two relays in the same mode (ex: two relays are set as 
PUMPs that FILL or two relays set as PUMPs that EMPTY).  Be sure to set one relay with an ON Set Point at the 
Primary Level and the other relay ON Set Point at the Backup Level.  Setting the relays with the same ON level 
will have cause both relays to turn on at the same time.  Once this is completed, see the steps below.  Example 
below shows two relays (A and B) used to Auto Empty a tank: 

 

1. Make  sure  at  least  two  relays  are  in  the  same 

mode for pumps.   
a. If  this  is  not  true,  then  M‐PLEX  will  not 

appear. 

2. In TOP‐LEVEL MENU mode, select M‐PLEX. 
3. Select DUPLEX. 

a. If  three  relays  are  configured  in  the  same 

mode, continue to step 4.   

b. If  only  two  relays  are  configured,  jump  to 

step 5. 

4. Select R1_R2 (Relay 1 & 2), R2_R3 (Relay 2 & 3) 

or R1_R3 (Relay 1 & 3). 
a. EchoSwitch®  will  allow  you  to  select  two  of 

three relays to duplex.   

5. Select EXIT to return to TOP‐LEVEL MENU. 

 
 


 
 
 
 

 