CONFIGURATION (cont.) 

Step Five 

How to set a LOW ALARM 

 

Before  starting,  measure  the  distance  from  the  bottom  of  the 
tank to the Low Alarm position (ON) in the tank. 

1. In  TOP‐LEVEL  MENU  mode,  select  RELAY1,  RELAY2  or 

RELAY3. 

2. Select ALARM. 
3. Select LOW. 
4. Using  the  UP  and  DOWN  buttons,  set  the  LOW  (ON)  set 

point for the relay. 

5. To  enter  the  value,  press  and  hold  SELECT  for  2  seconds 

and release.  SAVED will display. 

6. Select HYSTER to set the Hysteresis. 

a. Hysteresis  is  the  distance  away  from  the  original  ON 

setting where the Alarm will turn OFF. 

7. Using the UP and DOWN buttons, set the HYSTER (OFF) set 

point for the relay. 

8. To  enter  the  value,  press  and  hold  SELECT  for  2  seconds 

and release.  SAVED will display. 

9. Select EXIT to return to TOP‐LEVEL MENU. 

Note: The hysteresis (HYSTER) setting can be used to eliminate chattering of the relay. 

Note:  To speed up the scrolling of the values on the display, hold down the SELECT button while holding down 
the UP or DOWN buttons.
 

 

 

 