Flowline LU78 EchoSwitch User Manual

Page 21

Advertising
background image

Rev A 

MN300282 

21 of 34 

CONFIGURATION (cont.) 

Step Five 

How  to  Triplex  three  relays:    Triplex  enables  EchoSwitch®  to  use  three  relays  to  alternate  after  each  cycle 
while performing a lead lag‐lag operation.  To begin, configure all three relays in the same mode (ex: all relays 
are set as PUMPs that FILL or all relays set as PUMPs that EMPTY).  Be sure to set all three relay with different 
ON Set Point, one for Primary, one for Backup and the other for Backup 2).  Setting all three relays with the 
same ON level will cause the relays to all turn on at the same time.   Example below shows three relays (A, B 
and C) used to Auto Empty a tank: 

 

1. Make sure all three relays are in the same mode.  If this is not true, then TRIPLX will not appear. 
2. In TOP‐LEVEL MENU mode, select M‐PLEX. 
3. Select TRIPLX. 
4. Select EXIT to return to TOP‐LEVEL MENU. 

 

How to turn off M‐PLEX (DUPLEX or TRIPLEX) 

1. In TOP‐LEVEL MENU mode, select M‐PLEX. 
2. Select NO ALT. 
3. Select EXIT to return to TOP‐LEVEL MENU. 

 

 