INSTALLATION (cont.) 

Step Seven 

Fitting  Selection:    Check  the  part  number  to  determine  the  required  fitting  mount  size  and  thread  type.  
EchoSwitch® is commonly installed in tank adapters, flanges, brackets or standpipes.  Note: Always include the 
gasket when installing the EchoSwitch®
. 

1. Tank Adapter:  Select a tank adapter fitting, such as the LM52‐1890 for the LU74 Series or the LM52‐

2890 for the LU74 & LU78 Series.   

a. For  best  results,  select  a  2”  tank  adapter  and  add  a  reducer  bushing  such  as  the  LM52‐1400, 

thread x thread, reducer bushing.   

b. Avoid  tank  adapter  (thread  x  thread)  styles  and/or  pipe  stops  forward  of  the  installed 

transducer. 

c. Always mount the tank adapter so the majority of the fitting is outside the tank. 

i. Never  mount  the  tank  adapter  upside  down  or  the  bulk  of  the  material  is  inside  the 

tank. 

2” Tank Adapter 

Socket x Thread 

Tank Adapter 

w/ 2”x 1” Reducer Bushing 

Tank Adapter 

Thread x Thread 

 

Do not use thread x thread 

 

2. Riser:  Installations with tall, narrow risers can impede the acoustic signal.  

a. Core Out Concrete:  Applications where tank a concrete tank ceiling that has been cored out 

can  also  be  considered  as  a  riser  type  application.    In  these  applications  a  2:1  ratio  (Inner 
Diameter to Core Height) for the diameter of the core. 

b. LU74  &  LU78  Series:  2”  (5  cm)  diameter  risers  should  be  no  taller  than  5”  (12.7  cm).    Larger 

diameter risers should be no taller than 12” (30.5 cm). 

c. LU77 Series: 

 

Riser Specifications 

Inner 

Diameter 

Maximum 

Height 

2” (5cm) 

4” (10cm) 

6” (15cm) 

3” (7.6cm) 

8” (20cm) 

12” (30cm) 

Note: Do not exceed the dimensions listed above. 

 

 

Note:  If  attempting  to  raise  the 
sensor above the top of the tank 
to allow for a higher fill capacity, 
avoid the use of tall and narrow 
risers.    The  example  to  the  left 
exceeds  the  dimensions  listed  in 
the  Riser  Specifications  chart.  
Use a larger tank adapter which 
takes  into  account  the  Riser 
Specifications
.  

 