CONFIGURATION (cont.) 

Step Five 

How to configure the Operational range of EchoSwitch® 

 

Before  starting,  take  two  measurements.    1)  Measure  the 
distance from the bottom of the sensor (transducer face) to the 
bottom of the tank.  This will be the HEIGHT setting.  2) Measure 
the distance from the bottom of the tank to the Maximum Level 
of Liquid (Full).  This will be the FILL‐H setting.  

1. In TOP‐LEVEL MENU mode, select TANK. 
2. Select HEIGHT. 
3. Using  the  UP  and  DOWN  buttons,  set  the  HEIGHT  of  the 

tank (transducer face to the bottom of the tank). 

4. To  enter  the  value,  press  and  hold  SELECT  for  2  seconds 

and release.  SAVED will display. 

5. When FILL‐H appears, press SELECT. 
6. Using the UP and DOWN buttons, set the Fill Height (FILL‐

H)  of  the  tank  (max.  level  of  liquid  to  the  bottom  of  the 
tank).   

7. To  enter  the  value,  press  and  hold  SELECT  for  2  seconds 

and release.  SAVED will display. 

8. Select EXIT to return to TOP‐LEVEL MENU. 

Note:    The  Height  and  Fill‐Height  (Fill‐H)  settings  also  determine  the  4  to  20  mA  current  span.    The  Height 
setting determines the 4mA position and the Fill‐H setting determines the 20 mA position. 

Note:  To speed up the scrolling of the values on the display, hold down the SELECT button while holding down 
the UP or DOWN buttons. 

 


 

 